GF Solar Tracker Controller Passes 70℃ High-Temperature Test

  • Page view:67
  • Author:GF
  • 2025-08-11
To verify whether the solar tracker controller(TCU) device functions normally after high-temperature treatment. 


Experimental overview

▍Test Purpose:
- To verify whether the TCU device functions normally after high-temperature treatment.

▍Testing is conducted in accordance with the following standards:  
- The test procedures and criteria for evaluating test results are based on Chapter 16, Section 16.2 “High-Temperature Test” of GB/T 29320-2024 “Technical Requirements for Solar tracking systems in Photovoltaic Power Plants.”

Test Sample:
- Equipment Name: Tracking Control Unit (TCU)
- Model Specification: GF-S-TCU-V1.0 (GF-TCU-V1.0 DC Version)
- Quantity: 1 set

Test Date and Location:
- July 8, 2025
- No. 2 Courtyard, Southeast Corner of the Intersection of Dehui Street and Wenjin North Road, Zheng'an Town, Zhongmu County, Zhengzhou, Henan 

Test system:
- TCU control unit: Model GF-S-TCU-V1.0 (GF-TCU-V1.0 DC version), 1 set
- Tracking system type: Single-axis solar mounting system (including flat single-axis and inclined single-axis)  
- Tracking mechanism composition:  
· Electric Actuator: DC 24V motor with gear reduction mechanism    
· Steel Structure Mounting System, Flat Single-Axis, supporting ±60° rotation    
· Installation Components: 1P total of 9 solar panels

Experimental Equipment:
- High-Low Temperature Test Chamber

▍Environmental Conditions:
- Test Date: July 8, 2025  
- Test Location: Henan GF New Energy Technology Co., Ltd. factory test site  
- Ambient Temperature: 35.3℃
- Relative Humidity: 52% RH  
- Weather Conditions: Sunny, no significant wind interference



Test methods and procedures

▍Experimental Preparation:
- Connect the TCU to the tracking system
- The drive unit and control system of the tracking system are not powered on

Experimental Procedure Steps:
1. Place the drive unit and control system of the tracking system, which are not powered on, into the High-Low Temperature Test Chamber, and adjust the temperature of the test chamber to 70℃;
2. Store at 70℃ for 16 hours;
3. Gradually restore the temperature of the test chamber to 55℃ at a rate not exceeding 1℃/min, and let it stand at 55℃ for 2 hours;
4. Power on and operate for 2 hours, and record the operating status of the tracking system;
5. Let it work at room temperature for 2 hours;
6. Control the tracking system to operate in both automatic and manual modes, and record the operating status of the tracking system.



Test results and conclusions
 
Test Requirements   The TCU must be shut down and stored at 70℃ for 16 hours, then cooled to 55℃, and removed after 2 hours for room temperature testing.
Test Content Various operating mode 
tests and parameter settings 
 Tracking function Control function Protection and 
storage function
Communication and 
synchronization function
Tracking range and accuracy Drive unit
Test Results OK OK OK OK OK OK OK
Conclusion The TCU can function normally after High-temperature treatment.


















Test photos
 
TCU shuts up at 70℃ and stored for 16 hours.
















 
TCU cools to 55℃, shuts down, and stores for 2 hours.

 

 